Define what a duplicate means in this project
Start with the project tag convention and scope. A repeated string can be a legitimate reference to the same item on another sheet, an intentional annotation, or a true conflict between two distinct objects. Export or list object IDs, object classes, displayed tags, drawing numbers, and revisions before counting duplicates. Normalize spaces and punctuation in a separate field, while keeping the exact text seen on the drawing.
In Plant 3D, tag assignment can show existing tags, and validation can flag duplicated tags. The software checks structured project objects; it cannot establish that every label visible in an old raster scan was recognized correctly.
Audit in both directions
First, take a sample of exported tag records and locate each object on the controlled drawing. Check that class, tag, and nearby line or equipment association are correct. Then start from visible instrument bubbles and equipment symbols on the sheet and confirm that each has a record. The second direction finds omissions that a duplicate check cannot detect.
If the source is scanned, compare OCR results with crops of the original. Similar characters such as O and 0, I and 1, or a faint decimal point can change a tag. Keep low-confidence readings as review items, rather than normalizing them to the nearest familiar asset number.
- Duplicate: two distinct objects claim one tag within the project’s uniqueness scope.
- Missing: a visible instrument or equipment item has no corresponding record.
- Orphan: a tag or annotation has no confirmed associated object.
- Mismatch: the object class, line association, or register value disagrees with the drawing.
Check instrument relationships, not just bubbles
A bubble count is a useful reconciliation number, but it does not prove an instrument is connected correctly. Plant 3D validation can identify unconnected components, orphaned annotations, and other P&ID errors. Its documentation notes that a visually touching line and component may still lack a true connection. Check the signal or process line and the associated equipment for every critical instrument.
When a P&ID is only a PDF or ordinary AutoCAD geometry, its visible symbols do not automatically become intelligent P&ID objects. Treat extracted relationships as proposed links until an engineer verifies them against the drawing and asset register.
Deliver a short exception list
For each suspect record, include the tag as shown, proposed normalized tag, object class, drawing and revision, sheet location, issue type, and reviewer decision. Keep confirmed changes separate from unresolved readings. This creates a clear follow-up for the engineer and an auditable path back to the original sheet.